Sunday, October 24, 2010

DIL SINEWAVE UPS / INVERTER

DIL SINEWAVE UPS : UNIQUE FEATURES
  • Pure Sine Wave Inverter less 3% THD (Total Harmonic Distortion)
  • Based on DSP cutting edge Technology.
  • An Attractive and a very compact design to be part of your living room.
  • In built SMPS based charger with power factor correction to minimize the Power loss.
  • Constant 220v Out put voltage at any instant and at any load.
  • Mains Input output wrong connection protection.
  • Automatic Battery health check up and Bad Battery Detection by Battery intelligent software.
  • Visual indication with an Attractive LCD indicating load percentage, Battery voltage and Input output Voltage.
  • Suitable for solar charger.

DIL UPS / INVERTERS => Superior Quality, Low Price, Good Service

DIL SINEWAVE UPS is an extraordinary product, which is the perfect solution for Power failure &
Conservation of ENERGY. Business & Work depends on continuous Quality Power; avoid revenue losses
resulting from System failures / Excess ENERGY Consumption by Appliances.
“Saving one unit of Energy is equivalent as Generating two units of Energy”

FEW TIPS FOR THE CONSERVATION OF ENERGY

  • Always GO Green,opt for the Appliances which are ECO Friendly & Energy Efficient.
  • Use ISI Certified Electrical Appliances only.
  • Do not throw Batteries, Dry cells, Electronic Instruments / Appliances / Gadgets, these products contains LEAD(Pb), this will cause Dangerous Hazards when exposed to environment or manhandled or consumed by children, so always recycle these with the authorised Recycler only.
  • CFL’S gives more light & also saves more ENERGY; in turn Reduces Monthly Light Bills, so replace all your Tube Lights or Incandescent Bulbs today with the Energy Efficient CFL’S.
“Secure the future generation by Saving Energy, Save ENERGY, Save our Beautiful EARTH”

DIL provides continuous, ENERGY Efficient, Quality and clean power supply, for your precious time by adding the value for the tasks you perform & Saves more Power and ENERGY.

APPLICATIONS OF OUR PRODUCTS
  1. Computer – Desktop, Laptop, Server
  2. Data Switches, Modems
  3. Printer – Inkjet, Deskjet, Laser jet
  4. Scanners / Speakers
  5. Refrigerators / Air Conditioner / CNC Machines
  6. Compact Fluorescent Lamps ( CFL’S)
  7. Fluorescent Tube Lights / Incandescent Bulbs
  8. Mixer Grinder / Fans / Air Coolers
  9. DVD Player / Music Systems / Home Theatre Systems
  10. Television CRT & LCD / Dish Antenna / Digital Satellite TV
EXCLUSIVE FEATURES & ADVANTAGE OF OUR PRODUCTS
  • Advanced DSP based PWM technology
  • High efficiency to save energy and money
  • Dual purpose Inverter / UPS, (Opt. Solar Charger)
  • Reliable product for long durability
  • No separate wiring is required
  • Environment friendly
  • Noiseless operation hence no need canopy
  • Green mode SAVES POWER in no load conditions
  • Pure Sinewave Output ( No Distortion)
  • Cold and soft start operation to protect the load
  • Unmatched Product capability
  • User friendly Digital LCD Display for Clear Information
  • Display shows Machine Fault & Call Service
  • Compact & Aesthetic Design
  • Computer & Lighting Mode
  • Space Saver
  • Zero Maintenance
  • 24 x 7 Customer Support
OPTIONAL FEATURES ON DEMAND
  1. RS 232 Interface
  2. Solar Photo Voltaic Cell Charging Support
  3. No Load Sleep & Wakeup
PROTECTIONS & SAFETY
  1. Self-Diagnostic Support on Every Start Up
  2. Intelligent Battery Analyzer, Intelligent Auto Reset Function
  3. High Voltage Protection, Low Voltage Protection
  4. Output Short Circuit OFF, Over Load Cut OFF
  5. Auto Bypass in case of Failure
  6. Output / Input Phase Reversal Protection
  7. Temperature Sensor for Protection of Components

DIL Contact us

Contact DIL

Head Office :

Digidon India Labs

184, 1st A Main, Kengeri Satellite Town,

Bangalore 560060

Karnataka, INDIA

Contact : Mahendra G Prasaad

Ph : +91 9740260066

E-mail : digidon@in.com

website : 


DescriptionSales & Service Support : Home Inverter / UPS, Solar UPS, OFF-line UPS, ON Line UPS, Inverters, UPS & Batteries, Stabilizers, Computer Desktops, Laptops, Servers, SMPS, Chargers,
Emaildigidon@in.com
Payment AcceptedBank Wire, Cheque, Cash
Area servedNational Association for the Blind, HAL 3rd Stage, New Thipasandra, Bengaluru, Karnataka, India 20.0 miles from in and around Bangalore
Categories:Used Computer Laptop Store, Computer Repair Service, UPS / Inverter / Battery / Solar Lighting System Dealers, 24 Hours Customer Service Support, UPS / Inverter / Computer / Laptop / Service Centre
Hours:
Mon06 am11:30pm
Tue06 am11:30pm
Wed06 am11:30pm
Thu06 am11:30pm
Fri06 am11:30pm
Sat06 am11:30pm
Sun06 am11:30pm


DIGIDON INDIA LABS : About us

About DIL


Digidon India Labs (DIL) started operations in 2001 to provide technical services in various fields of electronics & computer science. We are into Embedded Systems, Research & Development, Power Electronics and Business Service Support. DIL provides complete support in Power electronics & Information Technology.


Company Overview: DIL is the company which uses the current technology & deliver new products, basically Research & development in the field of Electronics & computer tech, also the exclusive manufacturers of the DIGITAL technology UPS & INVERTERS with the new & Latest Technology with the LCD Display & Very Light weight UPS / Inverters, its Based in BENGALURU,

Products:

  • UPS & Inverter Manufacturers
  • UPS Off Line
  • UPS On Line
  • Ups AMC
  • Batteries
  • UPS Installation Services
  • Computer Hardware & Software Expert Installation
  • Solar UPS
  • Solar Lighting System
  • Second Hand Computer Laptop Buyers
  • Second Hand Computer Laptop Dealers
  • Computer Laptop Repairs & Services
  • Computer Desktop Repairs & Services


DIGIDON

DIGIDON BATTERY life enhancer™ (REVITALISER)

DIGIDON BATTERY life enhancer™ (REVITALISER)
  • WHY batteries die / FAILS :
The Lead plates are the HEART of the BATTERIES. Basically, the batteries are able to store and supply energy because of an interaction between the plates and the BATTERY acid. in theory, batteries should last years, but they usually don`t. Because of a series of problems caused by sulphation buildup. As the BATTERY gets older or sits unused for long period of time, LEAD SULPHATE on the BATTERY plates enlarge and buildup to the point where they create an insulation barrier. Before long, the buildup can become so dense that the BATTERY will no longer accept or release energy. DIGIDON BATTERY life enhancer™ (REVITALISER) anti sulphation system will help prevent this problem once and for all.
  • HOW DOES DIGIDON BATTERY life enhancer™ (REVITALISER) WORKS :
DIGIDON BATTERY Revitaliser Generates 15,000 Specific Electric Pulses per second, into the BATTERY. These pulses attack and activate the SULPHATE molecules that adhere to the LEAD plates inside whenever the BATTERY is discharged, preventing those molecules from crystallizing and permanently attaching to the LEAD plates. In this way, DIGIDON BATTERY life enhancer ™ Prevents Permanent sulphation in the BATTERY. The Pulses are so effective, that they also to a certain extent resolve already crystallized SULPHATE in old batteries. The SULPHATE is reactivated and brought back to the electrolyte as active material, rejuvenating the BATTERY.
  • how to measure the efficiency of the DIGIDON battery revitalizer :
You can measure the efficiency of the DIGIDON BATTERY life enhancer™ by yourself, by using a simple device which measures the specific gravity of the acid electrolyte in the battery using HYDROMETER (consult your nearest Service station or Retailer). First measure the acid concentration, then mount the DIGIDON BATTERY life enhancer™. After 2-3 months, measure the concentration again. A BATTERY in good condition has a specific gravity of approx., 1.26-1.30. If the concentration is less than 1.24, the battery is sulphated and the capacity is reduced to around 50%. Make sure that the measurements are done only when the BATTERY is fully charged.
  • BENEFIT USING DIGIDON BATTERY life enhancer™ :
Sulphation is the most common cause for the BATTERY FAILURE. It makes the battery last only a limited period of time. The internal parts of the BATTERIES are designed and produced to last for a much longer period of time. In other words, batteries could last much longer than they usually do.
A clean battery, provided by the DIGIDON BATTERY life enhancer ™ gives the following benefits:
  • Several extra years of operation.
  • Increased capacity, that contributes to more starting power (SURGE).
  • Reduced production, transport and disposal of environment friendly material (a problem even those batteries that are actually recycled)
  • When using the DIGIDON BATTERY life enhancer ™, you are using the environment & Eco Friendly.
DIGIDON BATTERY life enhancer™ (REVITALISER)
v  The following photographs were taken while the research was going on, the first is the photo of the spoiled Sulphated Battery, and the other is the photo of the Battery after the DIGIDON BATTERY life enhancer ™ connected for just three months, the results were amazing, even the spoiled Sulphated Battery was almost as good as the two-year old Battery. Four years Research has become success story now.
BATTERY INSIDE VIEW : BEFORE
*********************************************************************************************************
BATTERY INSIDE VIEW : AFTER

DIGIDON INDIA LABS : Battery Servicing Tips…

DIL : Battery Servicing Tips – Courtesy : Exide Batteries.

The ways & means to increase the life and performance of lead-acid batteries
  • The most important part is the care during initial filling and charging which determines the life & performance and knowledge about how a lead-acid battery works.
  • Followed by proper and regular routine and preventive maintenance of the battery banks.
  • To take corrective measures, one must have the knowledge of the normal failure modes of lead acid batteries & the reasons for the failure.
  • If any one is conversant of the failure mode and the reason for same, then will be in a position to rectify / prevent before it is too late.
  • Initial filling & charging (IFC)
General requirement
  • The battery room should be clean, dry & cool, with proper lighting & ventilation. Batteries to be cleaned before initial filling.
  • Matching constant current charger, should be available capable to supply requisite volt & amps designed to give at 6% rate of charge up to 2.75 VPC at toc voltage.
  • Sufficient quantity of battery grade sulphuric acid of 1.220 + 0.005 sp. Gravity at 27ºc conforming to be 266 & battery grade water conforming to be 1069 should be available. Some stock of 1.400-sp.gravity sulphuric acids at 27ºc for adjustment after full charging, if required.
  • Don’t use the blind plugs supplied with batteries. Keep the vent plugs loose in position, to avoid explosions.
  • Caution: do not use any metallic vessel, only use plastic vessel & protective wears. Never take open flame near cells. Never connect the cable loosely with the cells / batteries to avoid sparks & chance of explosion / melting.
General requirement: Making dilute Acid
  • If dilute acid prepared from concentrated acid at site, care to be taken. Do not use wooden or any other metal stirrer but to use plastic/lead ined wooden oar only to aviod contamination. Compressed air can be used for mixing but care should be taken to trap oil acid to be used.
  • To follow all laid down safety rules for diluting acid from 1.840-concentrated acid.
  • The acid to be used after cooling, sp. Gravity corrected to 27ºc.
  • Use ‘acifil pump’ or siphoning with spring loaded control lever trap, during acid filling to avoid spillage and surface / earth leakage.
Acid Filling Procedure:
  • The battery physically for any damages/visible cracks and cleaned prior to filling of acid.
  • Check the sp. Gravity of acid of all the Jerry cans corrected to 27ºc prior to filling.
  • Pour cool dilute battery grade sulphuric acid of 1.220/1.190 sp. Gravity up to the max. level by ‘acifil pump’, siphoning pipe or with funnel & jug carefully. Do not over fill to avoid spillage.
Polarity check & Rest period Procedure:
  • Just after acid filling, to check polarity of the cells by checking the voltage of all the cells, if any cell wrongly reverses assembled. The voltage observed is not that important at this point. Also check for any leakage visible after filling.
  • Allow 12 hours rest for the cooling; allow the plates & separators to soak acid, but not more than 24 hours. Top up again with acid, same as filling in sp. Gravity.
Putting on First Charge Procedure:
  • Use only DC ‘constant current’ charger only for initial charging of batteries.
  • Ensure the charger in working condition and capable of supplying requisite volt & amps required for the batteries to be charged.
  • Take care of polarity and connect the pos. Terminal of batteries with the pos. & neg. Terminal with neg. Of the charger, respectively.
  • Charging may be done in 2 steps or single step. In our tropical country advisable to charge in single step, specially in summer – For ‘2 step charging’ the initial current to be 12% of the C10 capacity of battery upto 2.36 VPC and followed by 6% of the C10 rated capacity of the battery upto 2.75 VPC. (For 500Ah battery 60 amps & 30 amps respectively). – For ‘single step’ charging, the battery to be charged continuously at the current 6% of the C10 rated capacity of the battery upto 2.75 VPC, till the end of charging e.g. 30 amps upto 2.75 VPC for a 500 Ah battery till end.
Condition of Fully Charged Procedure:
  • To continue DC charging at ‘constant current’ till the following conditions of fully charged cells are observed:
  • All cells are gassing freely at toc voltage, 2.75 VPC at 6% – the finishing rate.
  • No rise of voltage for 3 to 4 consecutive hourly readings, after reaching 2.75 VPC
  • No rise of sp.Gravity for 3 to 4 consecutive hourly readings, after reaching 2.75 VPC
  • Theoretical Ah input to be kept at the back of the mind- the input to be approx. 4.5 to 5 times of the Ah capacity of the battery i.e. For a 500 Ah battery the total Ah input to be 2250 Ah to 2500 Ah. (approx.time 75 to 85 hours)
Checks & Record during charging Procedure:
  • The electrolyte temperature should not be allowed to increase beyond 50ºc, during charging if the temperature goes above 50ºc, the charging to be suspended till the temp. of electrolyte comes down to 40º c, then only start the charging again.
  • Record the readings of sp. Gravity, voltage and the electrolyte temp. of cells, initially every 4 hourly and every hourly, after the cell voltage reaches 2.4 VPC.
First C10 Capacity test Procedure:
  • Batteries now charged ready – give a rest period of 12 hours for cooling & settling but not more than 24 hours.
  • Connect the batteries with suitable load and conduct C10 capacity test at constant current, upto ‘end voltage’ 0f 1.85 VPC e.g. For a 500 Ah battery at 50 amps for 10 hours. Take hourly readings and record the volt, sp. Gr.& electrolyte temp. Of all cells. If any cell voltage comes to 1.85 volt before 10 hours, the cell to be recharged / checked before taking for commissioning.
Recharge after C10 Capacity test Procedure:
  • Recharge the batteries immediately after discharge by constant current charging at 6% of the rated Ah capacity of the battery upto 2.75 VPC, till the batteries are fully charged- i.e. All cells are gassing freely, constant voltage, constant sp. Gr., theoretical 130% Ah input given, when 100% of Ah taken out during discharged.
Adjustment of Sp. Gravity Procedure:
  • After batteries are fully charged, the sp. Gravity of the electrolyte of all cells to be adjusted to the service gravity i.e. 1.210 /1.250 ± 0.005, at 27ºc. the batteries to be put on charge for proper mixing.
  • If sp. Gravity in cells more than service gravity corrected to 27ºc. Take out acid and add battery grade water, when on charge for proper mixing.adjust sp. Gravity to the service gravity corrected to 270 c. As applicable with respective batteries.
  • If the sp. Gravity of the cells less than the service gravity at 270 c take out acid and add 1.400 sp. Gr. Acid by few drops, on charge for proper mixing. Adjust the sp. Gravity to the service gravity at 270 c as applicable.
  • After adjustment of the specific gravity, continue the charging for 1- 2 hours for proper mixing of the electrolyte. Stop the charging and allow the batteries to cool, before commissioning.
  • The normal failure modes of lead – acid batteries
  • Sulphation in cells
  • Over discharge
  • Allowing a battery to stand idle
  • Starvation
  • Allowing electrolyte to fall below the top of plates
  • Impurities
  • Adding acid instead of water
Bucking of plates:
  • Over discharge
  • Continued operation with battery in starved condition
  • Charging at high rates
  • Non- uniform distribution of current over the plates, due to repeated deep discharge
  • Shedding of active materials
  • Normal shedding
  • Excessive charging rate, or overcharging
  • Charging sulphated plates at too high rate
  • Charging only a part of the plate
  • Deep discharge battery on normal charge.
  • Freezing.
  • Container trouble
Rough handling: any storage battery to be handled as if made of glass, though the containers made with hard rubber, SAN or FRP. Heavy batteries should be handled by more than one person or by mechanical handling and not to be dropped / dragged. This will lead container crack/ damage.
Explosion in cell: may cause due to open flame, electrical sparks and clogged vent holes.
Bulging of container: this is be due to under curing of the container.
  • Stacking should be restricted to max. 3 high, with hard board in between layers
  • Terminals/ connector corrosion
  • Too much topping water added to cells
  • Battery poorly sealed
  • Loose vent caps / float guide
  • Electrolyte spillage
  • Battery cable damaged, or loose
  • Connecting bare wires directly to battery terminals.
  • Loose terminal connections
  • Non application or renewal of petroleum jelly for protection
  • Loss of capacity
  • Impurities in the electrolyte
  • sulphation
  • Loose active materials
  • Incorrect proportions of acid and water in the electrolyte
  • Separators clogged
  • Shedding
  • Low level of electrolyte
  • Effect of age
  • Internal short-circuit
  • Worn out separators
  • Lead run
  • Foreign material
  • Accumulation of sediment
  • Reversal of plates
  • Assembling of the cell in reverse direction.
  • Charging a battery in wrong direction.
  • Lagging / defective cell in battery bank will be reversed if not taken care in time
  • Earth / surface leakage in battery
  • Over filling of battery water.
  • Careless hydrometer use, spillage of electrolyte.
  • Careless acid filling during initial filling & charging.
  • High sp. Gravity of electrolyte
  • Over filling of battery water.
  • Low sp. Gravity of electrolyte
  • High level of electrolyte
  • Low level electrolyte
  • Impurities
The importance of ‘equalising charge
  1. To ensure that every cell in a battery bank is maintained in healthy state to give enhanced life & performance it is advisable to give ‘equalising charge’ atleast once in a year.
  2. Under ‘constant potential’ mode during operation a passive layers form on the plates. This causes variation of sp.gravity & voltage from cell to cell.
  3. To take care the battery bank to be put on ‘constant current charging at 6% of rated capacity upto 2.75VPC, followed by an extended charge for 12 to 24 hours on ‘constant current’ charging at 3% of rated capacity. By this the cells are rejuvenated with fresh layer of active material, all the cells will show approx. Same sp. Gravity & voltage.
  4. As low current was given during 3% rated amps of the Ah capacity.
  5. This will not affect the activated portion of the plates, but will remove the patches of sulphate from the plates back to the solution, increasing the sp. Gravity of cells. so, it is mandatory to give equalising charge, once in a year, if not earlier.